TP Series
TP Series

The TP series provides pressure and temperature sensors in a single robust and light package. The TP series is ideal for realtime accurate superheat measurement.

Features
  • Accurate Real-Time Superheat Measurement
  • Wide Temperature Range
  • Simultaneous Pressure and Temperature
  • In-flow Media Temperature Measurement
Applications
  • HVAC
  • Commercial Refrigeration
  • Heat Pumps
  • Compressors
  • Hydraulics

Descriptions

  • TECHNICAL SPECIFICATIONS

    Accuracy @ 25°C (linearity, repeatability, hysteresis, and calibration)
    ±0.5 %Span
    Total Error Band
    ±1.0 %Span 0°C to 80°C
    ±1.5 %Span -20°C to 125°C 
    Pressure Ranges
    0-15 PSI through 0-750 PSI (absolute or sealed gage)
    Operating Temperature Range
    -40°C to 125°C
    Storage Temperature Range
    -40°C to 150°C
    Proof Pressure
    3X rated pressure (Maximum 1500 psi)
    Burst Pressure
    5X rated pressure (Maximum 2500 psi)
    Cycle Life
    >1 Million FS cycles
    Vibration
    5g (33Hz)
    Drop (any axis)
    1 m
    Housing Materials
    Brass* or Aluminum
    Electrical Connection
    Yazaki 4-pin, TE AMP-quadlok
    Protection
    IP67
    Media
    Refrigerant 
    Sealing Material
    Neoprene (Consult factory for other seal material options)
    Approvals and Marks (UL Listed File E480159, Class III)


  • ELECTRICAL SPECIFICATIONS


    Min Typ
    MaxUnit
    Supply Voltage (Vsupply)
    4.75
    55.25VDC
    Supply Current @ 3V
    -68mA
    Output Voltage (ratiometric 1)
    10% to 90% typical, other ranges are available
    Vsupply
    Upper Clipping Level
    --95%

    Lower Clipping Level
    5%
    --Vsupply
    Overvoltage Protection
    --16VDC
    Reversed Polarity Protection
    -16V--VDC
    Short Circuit Protection (Vo to Vsupply, Vo to ground)
    -Yes-
    Output Load
    -10-KΩ
    Insulation Resistance @ 500VDC for 1 minute
    100--MΩ
    Dielectric Strength
    -1800 for 1 sec
    -VAC
    Response Time
    -< 5-ms
    IEC61000-4-2 ESD
    ±2KV Terminal / ±8KV Contact Discharge / ±15KV Air Discharge
    IEC61000-4-3 Radiated
    50V/m (80-1000MHz)

    IEC61000-4-4 Transient/Burst
    1KV



    IEC61000-4-6 Conducted
    3V



* Standard

  • TEMPERATURE SPECIFICATIONS


    Min Typ
    MaxUnit
    Temperature Sensor type
    NTC (negative temperature coefficient )
    Resistance at 25°C

    10
    KΩ
    B-constant 25°C/50°C-3380
    -K
    B-constant 25°C/85°C (reference value)
    3434
    K
    B-constant 25°C/100°C (reference value)
    3455

    K
    Resistance Value tolerance @25°C

    ± 1%


    B-constant (25C/50°C) tolerance

    ± 1%